RCD tripping range for Alfen Twin Chargers

This article explains the RCD tripping criteria on Alfen Twin chargers.

RCDTripCriteria


All our products EV chargers comply to NEN:1010 (Netherlands), where we have the requirements for RCD operation and disconnection times.

The product standard for EV charging points, IEC 61851-1 provides two approaches:

In the Twin charger, a deliberate choice was made to use a Type B RCCB. 

This complies with IEC 62423, which is also referenced by NEN 1010.

IEC 62423 distinguishes between:
•    4.1 AC residual currents: refers to IEC 61008-1 (and IEC 61009-1)
•    4.2 DC residual currents

An example of tripping criteria for a 30 mA Type B RCCB (63 A) used in our chargers:


AC residual current
•    30 mA → < 300 ms
•    60 mA → < 150 ms
•    150 mA → < 40 ms


DC residual current
•    60 mA → < 300 ms
•    120 mA → < 150 ms
•    300 mA → < 40 ms